As data centers evolve to support AI, edge computing, and high-density cloud architectures, the challenge is no longer just maintaining an optimal power usage effectiveness (PUE), it is about achieving thermal reliability with unprecedented compute loads. Direct-to-chip liquid cooling continues to push the envelope on heat transfer performance, but one underestimated element in overall system reliability is the material composition of the fluid conveyance network itself. The hoses and fittings that transport coolant through these systems operate in extreme thermal and chemical environments, and their design directly influences uptime, maintenance intervals, and total cost of ownership.
Why Material Selection Matters
At its core, a liquid cooling system is only as reliable as its weakest component. If hoses, fittings, or seals fail due to poor material compatibility, the result could be leaks, contamination, or shortened system life, leading to downtime and costly remediation. Rubber, and rubber-like, materials are critical in hose assemblies, as they must balance flexibility for installation and serviceability with long-term resistance to temperature, pressure, permeation, coolant and coolant additives.
The challenge lies in the fact that not all rubbers, or rubber-like materials, are created equal. Each formulation is a complex recipe of polymers, plasticizers, fillers, and curing agents designed to deliver specific performance characteristics. The wrong selection can lead to issues such as fluid permeation, premature aging, or contamination of the coolant. In mission-critical environments like data centers, where even minor disruptions are unacceptable, this risk is magnified.
Temperature and Chemical Compatibility
Although data center cooling systems typically operate at temperatures between 45°C (113°F) and 65°C (149°F), sometimes reaching 100°C (212°F), those ranges can stress certain materials. Nitrile rubber, for example, performs well in oil-based environments but ages quickly in water-glycol systems, especially at higher temperatures. This can cause hardening, cracking, or coolant contamination.
By contrast, ethylene propylene diene monomer (EPDM) rubber has excellent resistance to water, glycols, and the additives commonly used in data center coolants, such as corrosion inhibitors and biocides. EPDM maintains its properties across the required operating range, making it a proven choice for direct-to-chip applications.
However, not all EPDM is the same. Developing the right EPDM for the application demands a deep understanding of polymer chemistry, filler interactions, and process control to precisely balance flexibility, heat resistance, and long-term stability.
Additionally, two curing processes, sulfur-cured and peroxide-cured, produce different performance outcomes. Sulfur-cured EPDM, while widely used, introduces zinc ions during the curing process. When exposed to deionized water, these ions can leach into the coolant, causing contamination and potentially degrading system performance. Peroxide-cured EPDM avoids this issue, offering higher temperature resistance, lower permeation rates, and greater chemical stability, making it the superior choice for modern liquid cooling.
Even among peroxide-cured EPDM compounds, long term performance is not uniform. While the cure system defines the crosslink chemistry, other formulation choices, particularly filler selection and dispersion, can influence how the material performs over time.
The use of fillers and additives is common in rubber compounding. These ingredients are often selected to control cost, improve processability, or achieve certain performance characteristics such as flame resistance, strength, or flexibility.
The challenge is that some filler systems perform well during initial qualification but are not optimized for long-term exposures faced in the operating environment. Certain fillers or processing aids can slowly migrate over time, introducing extractables into the coolant or subtly altering elastomer properties. For data center applications, EPDM compounds must therefore be engineered with a focus on long term stability, reinforcing why EPDM should not be treated as a commodity material in critical cooling systems.
Risks of Non-Compatible Materials
Material incompatibility can have several cascading effects:
- Contamination – Non-compatible materials can leach extractables into the coolant, leading to discoloration, chemical imbalance, and reduced thermal efficiency.
- Permeation – Some rubbers allow fluid to slowly migrate through the hose walls, causing coolant loss or altering the fluid mixture over time.
- Premature Failure – Elevated temperatures can accelerate aging, leading to cracking, swelling, or loss of mechanical strength.
- Leakage – Rubber under compression may deform over time, jeopardizing seal integrity if not properly formulated for resistance to compression set and tear.
In a recent two-week aging test at 80°C using a water-glycol coolant, hoses made of nitrile and sulfur-cured EPDM showed visible discoloration of the coolant, indicating leaching and breakdown of the material. Peroxide-cured EPDM, on the other hand, maintained stability, demonstrating its compatibility and reliability in long-term data center applications.
The Gates Approach
Drawing on lessons from mission critical industries that have managed thermal challenges for decades, Gates engineers apply material science rigor to the design of liquid cooling hoses for data center applications.
Rather than relying solely on initial material ratings or short-term qualification criteria, Gates begins by tailoring compound design to the operating environment. This includes deliberate control of polymer selection, filler systems, and cure chemistry to manage long term aging behavior, extractables, permeation, and retention of mechanical properties over time in high purity coolant systems.
Compounds are validated through extended aging and immersion testing that reflects real operating conditions, including exposure to heat, deionized water, and water-glycol coolants. This allows potential material changes to be identified and addressed during development, before installation in the field.
This material science driven process is applied across Gates liquid cooling platforms, including the Data Master, Data Master MegaFlex, and newly released Data Master Eco product lines. By engineering for long term stability rather than only initial compliance, Gates designs hose solutions intended to support reliable operation, predictable maintenance intervals, and extended service life in direct-to-chip liquid cooled data center environments.
Looking Ahead
As data centers continue to scale, thermal management solutions must adapt in parallel. Advanced architectures, higher rack densities, and growing environmental regulations all point to a future where liquid cooling is standard. In this environment, material selection is no longer a secondary consideration; it is foundational to system reliability.
Operators who prioritize material compatibility in fluid conveyance lines will benefit from longer service intervals, improved coolant stability, and reduced risk of downtime. In other words, the proper rubber formulation doesn’t just move fluid, it moves the industry forward.
At Gates, sustainable, high-performance cooling begins with the details. By focusing on the science of materials, we help ensure that data center operators can confidently deploy liquid cooling systems designed for the challenges of today and the innovations of tomorrow.
# # #
About the Author
Chad Chapman is a Mechanical Engineer with over 20 years of experience in the fluid power industry. He currently serves as a Product Application Engineering Manager at Gates, where he leads a team that provides technical guidance, recommendations, and innovative solutions to customers utilizing Gates products and services.
Driven by a passion for problem-solving, Chad thrives on collaborating with customers to understand their unique challenges and deliver solutions that optimize performance. He is energized by learning about new applications and technologies, especially where insights can be shared across industries. At Gates, he has been exploring the emerging field of direct-to-chip liquid cooling, an exciting extension of his deep expertise in thermal management. The rapid advancements in IT technology and AI have made his journey an inspiring and rewarding learning experience.